8A Redundant Power Supply Module 5.1 V DC Output Voltage Modicon Quantum 140CPS22400

Large Image :  8A Redundant Power Supply Module 5.1 V DC Output Voltage Modicon Quantum 140CPS22400

Product Details:

Place of Origin: FR
Brand Name: Schneider
Model Number: 140CRP93100

Payment & Shipping Terms:

Minimum Order Quantity: 1
Price: negotiable
Packaging Details: New in original box
Delivery Time: 2-3 work days
Payment Terms: T/T, Western Union
Supply Ability: 100
Detailed Product Description
Brand: Schneider Model: 140CRP93100
Palce Of Origin: FR Type: Quantum I/O
Output Voltage: 5.1 V DC Module Format: Standard
Marking: CE Weight: 2 Lb
High Light:

plc power supply module

,

diode redundancy module

Redundant Power Supply Module 24V 8A Redundante Schneider Electric Modicon Quantum 140CPS22400

 

 

 

Specifications

Manufacturer: Modicon Quantum
Series: Power Supplies
Weight: 2 lb
Power supply type: Redundant
Input voltage: 24 V DC 20...30 V
Input current: <= 3800 mA
Inrush current: 25 A 24 V
  14 A 20 V
Input power interruption: 1 ms 20 V
  <= 100 ms
Associated fuse rating: 5 A slow-blow
Output voltage: 5.1 V DC
Power supply output current: 8 A redundant
Output overvoltage protection: Internal
Output overload protection: 2.3 x maximum rated input voltage for 1.3 ms
Power dissipation: 6 + (1.8 x Iout) where Iout is in A
Alarm output: 1 NC 6 A 220 V power supply fault
Local signalling: 1 LED green power (PWR OK)
Marking: CE
Module format: Standard

 

 

 
 
 

OTHER SUPERIOR PRODUCTS

Yasakawa Motor, Driver SG- Mitsubishi Motor HC-,HA-
Westinghouse Modules 1C-,5X- Emerson VE-,KJ-
Honeywell TC-,TK- GE Modules IC -
Fanuc motor A0- Yokogawa transmitter EJA-
 
Contact person: Anna
E-mail: wisdomlongkeji@163.com
Cellphone: +0086-13534205279
 
 
 
 
 
Similar Products
140DAI34000
140DAI35300
140DAI44000
140DAI45300
140DAI54000
140DAI54300
140DAI55300
140DAI74000
140DAI75300
140DAM59000
140DAO84000
140DAO84010
140DAO84210
140DAO84220
140DAO85300
140DDI15310
140DDI35300
140DDI35310
140DDI36400
140DDI67300
140DDI84100
140DDI85300
 
 
 
Environment
standards
CSA C22.2 No 142
UL 508
 
product certifications
CUL
FM Class 1 Division 2
 
resistance to electrostatic discharge
4 kV contact conforming to IEC 801-2
8 kV on air conforming to IEC 801-2
 
resistance to electromagnetic fields
10 V/m 80...2000 MHz conforming to IEC 801-3
 
ambient air temperature for operation
0...60 °C
 
ambient air temperature for storage
-40...85 °C
 
relative humidity
95 % without condensation
 
operating altitude
<= 5000 m
 
Offer Sustainability
Sustainable offer status
Green Premium product
 
RoHS (date code: YYWW)
Compliant - since 0901 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
 
REACh  
Product environmental profile  
Product end of life instructions
Available
 
Contractual warranty
Warranty period
18 months
 

 

 

 

 

Understanding and Using Cut Wire Detection

If the electrical current between the input and the sensor is more than 1 mA, the wire is detected as not cut. If this current is less than 1 mA, the wire is detected as broken and the corresponding input’s red LED is lit.
If you install dry contact sensors, the corresponding input’s red LED will be lit whenever the contact is open and the current will be at 0 mA. To solve this and use cut wire detection properly, Schneider Electric recommends installing a pull-up resistor on the sensors so that the minimum current of 1 mA will be reached. You can use a 15 kohms pull-up resistor or work out the value you need. See the sensor
example in the illustration above.

 

 

 

 

Illustration

The following figure shows the wiring diagram for the 140CRP93100 module

 

 

power supply: 24 VDC
fuse: 1 A fast blow fuse
pull-up resistor (in sensor example): 15 kOhms
NOTE: There is only one group of 16 inputs. All common 24 V are internally connected and all common 0 V are also internally connected. The two pins of a same input (e. g: pin 1 and 2 for input 1) are internally connected too so that you can use either the right pin or the left one.