Product Details:
Payment & Shipping Terms:
|
| Brand: | Schneider | Model: | 140CRA31200 |
|---|---|---|---|
| Palce Of Origin: | FR | Type: | Ethernet |
| Series: | Quantum I/O | Module Format: | Standard |
| Number Of Port: | 3 | Weight: | 2 Lb |
| Highlight: | analog interface module,diode redundancy module |
||
Redundant Power Supply Module Module Schneider Ethernet 140CRA31200 Quantum RIO Drop E/IP
| Manufacturer: | Modicon Quantum |
| Series: | Quantum I/O |
| Weight: | Ask |
| Product or component type: | Ethernet RIO drop adaptor |
| Number of port: | 3 |
| Integrated connection: | Ethernet IP/Modbus TCP (device network) |
| type: | Ethernet IP/Modbus TCP (service port) |
| Communication port: | Ethernet IP/Modbus TCP |
| protocol | |
| Communication service: | The input data are collected and published to the remote I/O head adaptor |
| Output modules are updated with the data received from remote I/O head adaptor | |
| Topology: | Daisy chain loop |
| Local signalling: | 1 LED red for I/O |
| 1 LED green for RUN | |
| 1 LED green/red for network communication status (Net Status) | |
| 1 LED green/red for module status (Mod Status) | |
| Product compatibility: | 140CRP31200 |
| Environmental characteristic: | Standard environment |
| Width: | 167 mm |
| Height: | 50 mm |
OTHER SUPERIOR PRODUCTS
| Yasakawa Motor, Driver SG- | Mitsubishi Motor HC-,HA- |
| Westinghouse Modules 1C-,5X- | Emerson VE-,KJ- |
| Honeywell TC-,TK- | GE Modules IC - |
| Fanuc motor A0- | Yokogawa transmitter EJA- |
| product certifications |
CE
C-Tick UL 508 |
|
|---|---|---|
| standards |
CSA C22.2 No 142
EN 55011 IEC 61000-4-16 |
|
| IP degree of protection |
IP20 conforming to EN 61131-2
IP20 conforming to IEC 60527 |
|
| overvoltage category |
Class I conforming to EN 61131-2
|
|
| ambient air temperature for operation |
32...140 °F (0...60 °C) conforming to IEC 60068-2-1
32...140 °F (0...60 °C) conforming to IEC 60068-2-2 |
|
| ambient air temperature for storage |
-40...185 °F (-40...85 °C) conforming to IEC 60068-2-1
-40...185 °F (-40...85 °C) conforming to IEC 60068-2-2 |
|
| vibration resistance |
3.5 mm constant amplitude (f=0.5...8.4 Hz) conforming to EN 61131-2
1 gn constant acceleration (f=8.4...150 Hz) conforming to EN 61131-2 |
|
| operating altitude |
6561.68 ft (2000 m)
|
|
| altitude transport |
9842.52 ft (3000 m)
|
|
| relative humidity |
93 % conforming to IEC 60068
|
| Category |
18155 - QUANTUM I/O & POWER SUPPLIES
|
|
|---|---|---|
| Discount Schedule |
PC21
|
|
| GTIN |
00785901932512
|
|
| Nbr. of units in pkg. |
1
|
|
| Package weight(Lbs) |
1.21
|
|
| Returnability |
Y
|
|
| Country of origin |
FR
|
| Sustainable offer status |
Green Premium product
|
|
|---|---|---|
| RoHS (date code: YYWW) |
Compliant - since 1107 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity
|
|
| REACh | ||
| Product environmental profile |
Available
|
|
| Product end of life instructions |
Available
|
| Warranty period |
18 months
|
|---|
The 140CRA31200 is an Ethernet RIO drop adapter in the Modicon Quantum family of PLCs. It is the adapter module located in any Quantum Ethernet I/O installation. A remote I/O drop can be connected directly to the main ring cable or to a sub-ring cable.
It has 3 ports, and two integrated connection types – an Ethernet IP/Modbus TCP Service Port and an Ethernet IP/Modbus TCP Device Network. The 140CRA31200 module exchanges data with the remote I/O head module which is the 140CRP31200. Output modules are updated with data received from the remote I/O adapter. The input data is then collected and published to the remote I/O head adapter. The protocol used in the exchange is EtherNet/IP. The remote I/O scanner views the module as a remote I/O adapter. The exchanges are deterministic, which means that the time it takes to resolve a remote I/O logic scan is predictable.
Because the 140CRA31200 has 3 external Ehternet ports, it has 3 MAC addresses (but only 1 IP address). two of the Ethernet ports allow implicit I/O exchanges with a remote I/O scanner adapter. An implicit I/O exchange has a maximum frame size of 1,400 bytes. The ports can be implemented alone or in adapter mode. A maximum of 31 140CRA31200 adapter modules can be used in a single Ethernet remote I/O network. Ensure that you carefully plan network topology.
The 140CRa31200 has 4 local signaling LEDs: 1 green for Run, 1 green/red for module status (Mod Status), 1 green/red for network communication status (Net Status), and 1 red for I/O. Its ambient air temperature for operation should be kept to between 0 to 60 °C. If you are storing your module, it should be keep to -40 to 85 °C. The module can comfortably operate at an altitude of 2000 meters above sea level.
Contact Person: Mila